Vega VEGADIF 65 Operating Instructions Manual page 51

Foundation fieldbus, differential pressure transmitter
Table of Contents

Advertisement

Min. adjustment with le-
vel
Max. adjustment with le-
vel
Min. adjustment with
density
VEGADIF 65 • Foundation Fieldbus
6 Adjustment with the indicating and adjustment module PLICSCOM
The span adjustment is finished.
Proceed as follows:
1
Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
0.00 %
=
0.0000 bar
0.0000 bar
2
Set the requested value with [+] and [->].
3
Confirm with [OK] and edit the requested bar value.
4
Set the requested bar value with [+] and [->].
5
Confirm with [OK] and move to max. adjustment with [->].
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
The min. adjustment is finished.
Proceed as follows:
1
Edit the % value in the menu item "Max. adjustment" with [OK].
100.00 %
=
0.5000 bar
0.0000 bar
Information:
When the instrument is not yet adjusted, then the display pressure for
100 % corresponds to the nominal measuring range of the sensor (in
the above example 500 mbar).
2
Set the requested value with [->] and [OK].
3
Edit the requested mbar value with [OK].
4
Set the requested value with [+] and [->].
5
Confirm with [OK] and move to the menu overview with [ESC].
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
The max. adjustment is finished.
For the min. adjustment with density, a filling of the vessel is not
necessary. The numeric examples are stated in chapter Mounting,
Measurement setup density and interface of this instructions manual.
Proceed as follows:
1
Edit the % value in the menu item "Min. adjustment" with [OK].
51