CHAPTER 5: SETTINGS
Operand type
Operand syntax
ELEMENT:
SWITCH 1 OFF CMD
Disconnect switch
SWITCH 1 ON CMD
SWITCH 1 CLOSED
SWITCH 1 OPEN
SWITCH 1 DISCREP
SWITCH 1 TROUBLE
SWITCH 1 ΦA CLSD
SWITCH 1 ΦA OPEN
SWITCH 1 ΦA BAD ST
SWITCH 1 ΦA INTERM
SWITCH 1 ΦB CLSD
SWITCH 1 ΦB OPEN
SWITCH 1 ΦB BAD ST
SWITCH 1 ΦB INTERM
SWITCH 1 ΦC CLSD
SWITCH 1 ΦC OPEN
SWITCH 1 ΦC BAD ST
SWITCH 1 ΦC INTERM
SWITCH 1 BAD STATUS
SWITCH 2 to 12
ELEMENT:
TELEPRO CH1 FAIL
Teleprotection
TELEPRO CH2 FAIL
TELEPRO CH1 ID FAIL
channel tests
TELEPRO CH2 ID FAIL
TELEPRO CH1 CRC FAIL
TELEPRO CH2 CRC FAIL
TELEPRO CH1 PKT LOST
TELEPRO CH2 PKT LOST
ELEMENT:
TELEPRO INPUT 1-1 On
Teleprotection
inputs/outputs
TELEPRO INPUT 1-16 On
TELEPRO INPUT 2-1 On
TELEPRO INPUT 2-16 On
ELEMENT:
THERMAL PROT 1 PKP
Thermal overload
THERMAL PROT 1 OP
protection
THERMAL PROT 2
ELEMENT:
TIME OF DAY 1 OFF
Time of day timer
TIME OF DAY 1 ON
TIME OF DAY 1 START
TIME OF DAY 1 STOP
TIME OF DAY 2 to 5
ELEMENT:
TRIP BUS 1 PKP
Trip bus
TRIP BUS 1 OP
TRIP BUS 2 to 6
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Operand description
Disconnect switch 1 open command initiated
Disconnect switch 1 close command initiated
Disconnect switch 1 is closed
Disconnect switch 1 is open
Disconnect switch 1 has discrepancy
Disconnect switch 1 trouble alarm
Disconnect switch 1 phase A is closed
Disconnect switch 1 phase A is open
Disconnect switch 1 phase A bad status is detected (discrepancy between
the 89/a and 89/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase B is closed
Disconnect switch 1 phase B is open
Disconnect switch 1 phase B bad status is detected (discrepancy between
the 89/a and 89/b contacts)
Disconnect switch 1 phase B intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase C is closed
Disconnect switch 1 phase C is open
Disconnect switch 1 phase C bad status is detected (discrepancy between
the 89/a and 89/b contacts)
Disconnect switch 1 phase C intermediate status is detected (transition from
one position to another)
Disconnect switch 1 bad status is detected on any pole
Same set of operands as shown for SWITCH 1
Channel 1 failed
Channel 2 failed
The ID check for a peer relay on channel 1 has failed
The ID check for a peer relay on channel 2 has failed
CRC detected packet corruption on channel 1
CRC detected packet corruption on channel 2
CRC detected lost packet on channel 1
CRC detected lost packet on channel 2
Flag is set, Logic =1
Flag is set, Logic =1
Flag is set, Logic =1
Flag is set, Logic =1
Thermal overload protection 1 picked up
Thermal overload protection 1 operated
Same set of operands as shown for THERMAL PROT 1
Time of day timer 1 is off
Time of day timer 1 is on
One-second pulse at set time of day timer 1 start time
One-second pulse at set time of day timer 1 stop time
Same set of operands as shown for TIME OF DAY 1
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
Same set of operands as shown for TRIP BUS 1
FLEXLOGIC
5
5-151