PRODUCT SETUP
Setting Groups
The UR implements a setting groups element as detailed in the Control Elements > Setting Groups section of this chapter.
The active setting group and the setting group open for edits can be selected via MMS commands SelectActiveSG and
SelectEditSG. The setting related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access
the setting that configures the IEC 61850 setting group commands.
5
Initial Setting Group
Range: 1 to 6 in steps of 1
Default: 1
The entered value sets the initial value of the non-volatile register normally controlled by the service SelectActiveSG. This
initialization occurs only on the UR reboot immediately following the receipt of a valid CID file.
This setting is not mapped into the IEC 61850 information model, but sets the value of SettingControl element attribute
actSG in SCL files.
Commands
The UR implements a number of clear records commands as detailed in the Commands and Targets chapter of this
manual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commands
are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings
that configure the IEC 61850 protocol interface for record clear commands.
5-80
Figure 5-34: Setting Groups panel
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS