CHAPTER 5: SETTINGS
Multiple LANS, no redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected, and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
5.3.4.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating
information, such as the serial number and order code of your device.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  NETWORK 1(3)
 NETWORK PORT 1
 NETWORK PORT 2
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-7: Multiple LANS, no redundancy
PRT1 IP ADDRESS:
127.0.0.1
PRT1 SUBNET IP MASK:
255.0.0.0
PRT1 FUNCTION:
Enabled
PRT2 IP ADDRESS:
127.0.0.1
PRT2 SUBNET IP MASK:
255.0.0.0
PRT2 REDUNDANCY:
None
PRP MCST ADDR:
01154E000100
PRT2 FUNCTION:
Enabled
Range: standard IPV4 address format
Range: standard IPV4 address format
Range: Enabled, Disabled
Range: standard IPV4 address format
Range: standard IPV4 address format
Range: None, Failover, PRP
Range if no PRP license: None, Failover
Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF
Range: Enabled, Disabled
PRODUCT SETUP
5
5-31