GE C70 Instruction Manual page 431

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
BREAKER RESTRIKE 1 HF DETECT
High-frequency pattern is typical for capacitor bank, cables, and long transmission lines applications.
— Assigns a FlexLogic operand indicating the open position of the breaker. It must be logic "1" when
BRK RSTR 1 BRK OPEN
the breaker is open. It is important to assign either 52 contact with this setting or breaker close command with
setting to give clear indication to the relay about breaker status.
CLS CMD
— Assigns a FlexLogic operand indicating a breaker open command. It must be logic "1" when the
BRK RSTR 1 OPEN CMD
breaker is opened, either manually or from protection logic.
— Assigns a FlexLogic operand indicating a breaker close command. It must be logic "1" when the
BRK RSTR 1 CLS CMD
breaker is closed.
5.8.10.5 VT fuse failure
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  VT FUSE FAILURE 1(6)
 VT FUSE FAILURE 1
Every signal source includes a fuse failure scheme.
The VT fuse failure detector is used to raise an alarm and/or block elements that operate incorrectly for a full or partial loss
of AC potential caused by one or more blown fuses. Some elements that can be blocked (via the BLOCK input) are distance,
voltage restrained overcurrent, and directional current.
There are two classes of fuse failure that occur:
Class A — Loss of one or two phases
Class B — Loss of all three phases
Different means of detection are required for each class. An indication of class A failures is a significant level of negative-
sequence voltage, whereas an indication of class B failures is when positive sequence current is present and there is an
insignificant amount of positive sequence voltage. Also, a rapid decrease in the phase voltages magnitude from a healthy
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
— Enables/disables high-frequency (HF) pattern detection when breaker restrike occurs.
Figure 5-145: Breaker restrike logic
VT FUSE FAILURE 1
FUNCTION: Disabled
VT FUSE FAILURE 1
ALARM DELAY: 1.000 s
NEUTRAL WIRE OPEN 1
DETECTION: Disabled
NEUTRAL WIRE OPEN 1
3 HARM PKP: 0.100 pu
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
Range: 0.004 to 3.000 pu in steps of 0.001
CONTROL ELEMENTS
BRK RSTR 1
5
5-265

Advertisement

Table of Contents
loading

Table of Contents