SPECIFICATIONS
Noise:

2.5.12 Type tests

C70 TYPE TESTS
Test
2
Dielectric voltage withstand
Impulse voltage withstand
Damped oscillatory
Electrostatic discharge
RF immunity
Fast transient disturbance
Surge immunity
Conducted RF immunity
Power frequency immunity
Voltage interruption and ripple DC
Radiated and conducted emissions
Sinusoidal vibration
Shock and bump
Seismic
Power magnetic immunity
Pulse magnetic immunity
Damped magnetic immunity
Voltage dip and interruption
Damped oscillatory
Conducted RF immunity, 0 to 150 kHz
Voltage ripple
Ingress protection
Cold
Hot
Humidity
Damped oscillatory
RF immunity
Safety
Safety
Safety
Safety
1 Not tested by third party.

2.5.13 Production tests

THERMAL
Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process.
2-32
0 dB
Reference standard
1
EN 60255-5
1
EN 60255-5
IEC 61000-4-18 / IEC 60255-22-1
EN 61000-4-2 / IEC 60255-22-2
EN 61000-4-3 / IEC 60255-22-3
EN 61000-4-4 / IEC 60255-22-4
EN 61000-4-5 / IEC 60255-22-5
EN 61000-4-6 / IEC 60255-22-6
1
EN 61000-4-7
/ IEC 60255-22-7
IEC 60255-11
CISPR11 / CISPR22 / IEC 60255-25
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
1
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
1
IEC 60529
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEEE/ANSI C37.90.1
IEEE/ANSI C37.90.2
UL 508
UL C22.2-14
UL 1053
IEC 60255-27
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTION
Test level
2.2 kV
5 kV
2.5 kV CM, 1 kV DM
Level 3
Level 3
Class A and B
Level 3 and 4
Level 3
Class A and B
12% ripple, 200 ms interrupts
Class A
Class 1
Class 1
Class 1
Level 5
Level 4
Level 4
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
2.5 kV CM, 1 kV DM
Level 4
15% ripple
IP20 front, IP10 back
–40°C for 16 hours
85°C for 16 hours
6 days, variant 1
2.5 kV, 1 MHz
20 V/m, 80 MHz to 1 GHz
e83849 NKCR
e83849 NKCR7
e83849 NKCR
Insulation: class 1, Pollution degree: 2, Over
voltage cat II