CHAPTER 5: SETTINGS
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
GGIO2 CF SPCSO 1 CTLMODEL
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control Virtual Input 1. "sbo" here is select-before-
operate.
GGIO2 CF SPCSO 2 CTLMODEL
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
Selects the control model for Virtual Input 2, and so on.
GGIO4
GGIO4 is a UR feature that allows up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information model
data attribute.
For the value of a FlexAnalog operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO4 allows those FlexAnalog operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the
settings for the first GGIO4 value. The settings and functionality for the others are similar.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-37: GGIO2 panel
PRODUCT SETUP
5
5-83