Back Up And Restore Settings - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

BACK UP AND RESTORE SETTINGS

for the file.
In the figure, the first entry (red) is from the device, while the second (green) is the default value.
10.5.2 Compare two devices
Preferences can be set under File > Preferences as follows:
Comparison Report: Sequential File 1, File 2 Layout — When disabled (default), the report shows only what differs, as
shown in the previous figure. When enabled, the report indicates differences by device.
Figure 10-6: Device settings compared between two devices, displayed sequentially
There are two ways to compare devices: devices in the Offline area or between Online and Offline devices.
To compare settings of two devices in the Offline Window area:
1.
Right-click a first device in the Offline Window area and select Compare Two Devices.
2.
In the window that opens, select a second device and click the Receive button. The file generates and the number of
differences displays.
3.
To save the report, click File > Save As, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.
To compare settings between Online and Offline devices:
1.
Right-click a device in the Online Window area and select Compare with Device.
2.
In the window that opens, enter a path/file name at the bottom o f the window.
3.
Select the second device.
4.
Click the OK button. The file generates, and the differences are highlighted in red, which is for the first device.
10.6 Back up and restore settings
Back up a copy of the in-service settings for each commissioned UR device, so as to revert to the commissioned settings
after inadvertent, unauthorized, or temporary setting changes are made, after the settings defaulted due to firmware
upgrade, or when the device has to be replaced. This section describes how to backup settings to a file and how to use
10
that file to restore the settings to the original relay or to a replacement relay.
10-6
Figure 10-5: Device settings compared with default values
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 10: MAINTENANCE

Advertisement

Table of Contents
loading

Table of Contents