Advertisement

CHAPTER 5: SETTINGS

5.7.6 Negative sequence current

5.7.6.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT
 NEGATIVE SEQUENCE
 CURRENT
5.7.6.2 Negative sequence time overcurrent (ANSI 51Q, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT  NEG SEQ TOC1
 NEG SEQ TOC1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-99: Ground IOC1 logic
 NEG SEQ TOC1
 NEG SEQ TOC2
 NEG SEQ IOC1
 NEG SEQ IOC2
 NEG SEQ DIR OC1
 NEG SEQ DIR OC2
NEG SEQ TOC1
FUNCTION: Disabled
NEG SEQ TOC1 SIGNAL
SOURCE: SRC 1
NEG SEQ TOC1
PICKUP: 1.000 pu
NEG SEQ TOC1
CURVE: IEEE Mod Inv
NEG SEQ TOC1
TD MULTIPLIER: 1.00
NEG SEQ TOC1
RESET: Instantaneous
NEG SEQ TOC1 BLOCK:
Off
GROUPED ELEMENTS
See below
See page 5-198
See page 5-199
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.020 to 30.000 pu in steps of 0.001
Range: see Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: FlexLogic operand