3.1

Electrical Specifications

These megohmmeters display the measurement every 400ms, which
corresponds to 2.5 measurements per second for the digital display. The
bargraph is refreshed every 100ms. The digital measurement is smoothed,
while the bargraph always indicates the instantaneous measurement.
Reference Conditions
Parameters
Temperature
Relative humidity
Supply voltage
Frequency of measured voltage
Frequency of measured current
Capacity in parallel on resistance
Electrical field
Magnetic field
3.1.1

Voltage

Measurement Range: 0 to 600V
Frequency: DC at 400Hz
Auto Ranging
Resolution
Accuracy
Input Impedance
3.1.2

Insulation

Measurement Range:
Model 1039:
Model 1035:
Shop for AEMC products online at:
20

SPECIFICATIONS

0.0 to 399.9V
50V 10kΩ to 400MΩ
100V 20kΩ to 400MΩ
50V
10kΩ to 2GΩ
100V
20kΩ to 2GΩ
www.
250V
50kΩ to 20GΩ
500V 100kΩ to 20GΩ
CHAPTER 3
Reference Conditions
23°C ± 3K
45 to 55% RH
8V ± 0.2V
DC, or 45 to 65Hz
DC, or 45 to 65Hz
nil
nil
< 40A/m
AC/DC
AC/DC
0.1V
±3% R ± 1ct
6MΩ (1039) - 300kΩ (1035)
ShopAEMC
Digital Analog Megohmmeter Models 1035/1039
400 to 600V
AC/DC
1V
.ca