B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 65)
ADDR
REGISTER NAME
78AC
...Repeated for PMU 2
78C8
...Repeated for PMU 3
78E4
...Repeated for PMU 4
Phasor Measurement Unit Recording Values (Read Only) (4 modules)
7900
PMU 1 Available Records
B
7901
PMU 1 Second Per Record
7903
PMU 1 Last Cleared Date
7905
...Repeated for PMU 2
790A
...Repeated for PMU 3
790F
...Repeated for PMU 4
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7914
PMU Network Reporting Function
7915
PMU Network Reporting ID Code
7916
PMU TCP Port Number
7917
PMU UDP Port Number 1
7918
PMU UDP Port Number 2
Phasor Measurement Unit Calibration (Read/Write Setting) (4 modules)
7919
PMU 1 Va Calibration Angle
791A
PMU 1 Va Calibration Magnitude
791B
PMU 1 Vb Calibration Angle
791C
PMU 1 Vb Calibration Magnitude
791D
PMU 1 Vc Calibration Angle
791E
PMU 1 Vc Calibration Magnitude
791F
PMU 1 Vx Calibration Angle
7920
PMU 1 Vx Calibration Magnitude
7921
PMU 1 Ia Calibration Angle
7922
PMU 1 Ia Calibration Magnitude
7923
PMU 1 Ib Calibration Angle
7924
PMU 1 Ib Calibration Magnitude
7925
PMU 1 Ic Calibration Angle
7926
PMU 1 Ic Calibration Magnitude
7927
PMU 1 Ig Calibration Angle
7928
PMU 1 Ig Calibration Magnitude
7929
PMU 1 Sequence Voltage Shift Angle
792A
PMU 1 Sequence Current Shift Angle
792B
...Repeated for PMU 2
793D
...Repeated for PMU 3
794F
...Repeated for PMU 4
Phasor Measurement Unit Triggering (Read/Write Setting) (4 modules)
7970
PMU 1 User Trigger
7972
...Repeated for PMU 2
7974
...Repeated for PMU 3
7976
...Repeated for PMU 4
Phasor Measurement Unit Current Trigger (Read/Write Setting) (4 modules)
7980
PMU 1 Current Trigger Function
7981
PMU 1 Current Trigger Pickup
7982
PMU 1 Current Trigger Pickup Time
7983
PMU 1 Current Trigger Dropout Time
7984
PMU 1 Current Trigger Block (3 items)
798A
PMU 1 Current Trigger Target
798B
PMU 1 Current Trigger Events
798C
...Repeated for PMU 2
7998
...Repeated for PMU 3
79A4
...Repeated for PMU 4
B-40
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 65535
---
0 to 6553.5
---
0 to 400000000
---
0 to 1
---
1 to 65534
---
1 to 65535
---
1 to 65535
---
1 to 65535
---
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-180 to 180
°
-180 to 180
°
0 to 4294967295
---
0 to 1
---
0.1 to 30
pu
0 to 600
s
0 to 600
s
0 to 4294967295
---
0 to 2
---
0 to 1
---
APPENDIX B
STEP
FORMAT
DEFAULT
1
F001
0
0.1
F003
0
1
F050
0
1
F102
0 (Disabled)
1
F001
1
1
F001
4712
1
F001
4713
1
F001
4714
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
30
F002
0
30
F002
0
1
F300
0
1
F102
0 (Disabled)
0.001
F001
1800
0.01
F001
10
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
GE Multilin