5 SETTINGS
Multiple LANS, with Redundancy
The topology in the following figure provides local configuration/monitoring through EnerVista software and access to the
public network shared on LAN1, to which port 1 (P1) is connected. There is no redundancy provided on LAN1. Communica-
tions to SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 is
the redundant channel. In this configuration, P3 uses the IP and MAC address of P2.
EnerVista Software
Multiple LANS, No Redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
EnerVista Software
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
Figure 5–5: MULTIPLE LANS, WITH REDUNDANCY
Public Network
LAN1
ML3000
ML3000
P1
P2
IP1/
IP2/
MAC2
MAC1
Redundancy mode
UR
Figure 5–6: MULTIPLE LANS, NO REDUNDANCY
Public Network
LAN1
LAN2
ML3000
ML3000
P1
P2
IP1/
IP2/
MAC2
MAC1
UR
SCADA
LAN2
LAN2
ML3000
P3
IP2/
MAC2
859709A4.vsd
SCADA
LAN3
ML3000
P3
IP3/
MAC3
859710A2.vsd