GE N60 Instruction Manual page 152

Ur series network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
When a 0 value is involved in a change, the changes to the
N60 is restarted.
NOTE
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
i) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 DNP PROTOCOL
5
5-36

COMMUNICATIONS
 DNP CHANNELS
DNP ADDRESS:
MESSAGE
1
 DNP NETWORK
MESSAGE
 CLIENT ADDRESSES
DNP TCP/UDP PORT
MESSAGE
NUMBER: 20000
DNP UNSOL RESPONSE
MESSAGE
FUNCTION: Disabled
DNP UNSOL RESPONSE
MESSAGE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MESSAGE
MAX RETRIES: 10
DNP UNSOL RESPONSE
MESSAGE
DEST ADDRESS: 1
DNP CURRENT SCALE
MESSAGE
FACTOR: 1
DNP VOLTAGE SCALE
MESSAGE
FACTOR: 1
DNP POWER SCALE
MESSAGE
FACTOR: 1
DNP ENERGY SCALE
MESSAGE
FACTOR: 1
DNP PF SCALE
MESSAGE
FACTOR: 1
DNP OTHER SCALE
MESSAGE
FACTOR: 1
DNP CURRENT DEFAULT
MESSAGE
DEADBAND: 30000
DNP VOLTAGE DEFAULT
MESSAGE
DEADBAND: 30000
DNP POWER DEFAULT
MESSAGE
DEADBAND: 30000
DNP ENERGY DEFAULT
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT
MESSAGE
DEADBAND: 30000
N60 Network Stability and Synchrophasor Measurement System
MODBUS TCP PORT NUMBER

DNP PROTOCOL
Range: see sub-menu below
Range: 0 to 65519 in steps of 1
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 60 s in steps of 1
Range: 1 to 255 in steps of 1
Range: 0 to 65519 in steps of 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
5 SETTINGS
setting take effect when the
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents