Rs422 Interface - GE N60 Instruction Manual

Ur series network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

3 HARDWARE
a) DESCRIPTION
There are three RS422 inter-relay communications modules available: single-channel RS422 (module 7T), dual-channel
RS422 (module 7W), and dual-channel dual-clock RS422 (module 7V). The modules can be configured to run at 64 or
128 kbps. AWG 24 twisted shielded pair cable is recommended for external connections. These modules are protected by
optically-isolated surge suppression devices.
The two-channel two-clock RS422 interface (module 7V) is intended for use with two independent channel banks
with two independent clocks. It is intended for situations where a single clock for both channels is not acceptable.
NOTE
The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:
Site 1: Terminate shield to pins 6a or 7b or both.
Site 2: Terminate shield to COM pin 2b.
Match the clock terminating impedance with the impedance of the line.
Single-channel RS422 module
~ indicates the slot position
The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.
Figure 3–33: TYPICAL PIN INTERCONNECTION BETWEEN TWO RS422 INTERFACES
b) TWO-CHANNEL APPLICATION VIA MULTIPLEXERS
The RS422 interface can be used for single channel or two channel applications over SONET/SDH or multiplexed systems.
When used in single-channel applications, the RS422 interface links to higher order systems in a typical fashion observing
transmit (Tx), receive (Rx), and send timing (ST) connections. However, when used in two-channel applications, certain cri-
teria must be followed since there is one clock input for the two RS422 channels. The system functions correctly when the
following connections are observed and your data module has a terminal timing feature. Terminal timing is a common fea-
ture to most synchronous data units that allows the module to accept timing from an external source. Using the terminal
timing feature, two channel applications can be achieved if these connections are followed: The send timing outputs from
the multiplexer (data module 1), connects to the clock inputs of the UR–RS422 interface in the usual fashion. In addition,
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
~
3b
Tx –
~
3a
Rx –
~
2a
RS422
Tx +
4b
~
Rx +
6a
~
Shield
7a
~
Clock
~
8b
~
2b
COM
Surge
~
8a
Figure 3–32: RS422 INTERFACE CONNECTIONS
3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS
Dual-channel RS422 module
~
3b
Tx –
~
3a
Rx –
RS422
~
2a
Tx +
channel 1
4b
~
Rx +
6a
~
Shield
5b
~
Tx –
~
5a
Rx –
RS422
~
4a
Tx +
channel 2
~
6b
Rx +
~
7b
Shield
~
7a
Clock
~
8b
~
2b
COM
~
8a
Surge
842776A3.CDR

3.3.5 RS422 INTERFACE

3-27
3