5.4 SYSTEM SETUP
c) CALIBRATION

PATH: SETTINGS
SYSTEM SETUP
CALIBRATION
 PMU 1
 CALIBRATION
5
This menu contains user angle and magnitude calibration data for the phasor measurement unit (PMU). This data is com-
bined with the factory adjustments to shift the phasors for better accuracy.
PMU 1 VA... IG CALIBRATION ANGLE: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
5-116

PHASOR MEASUREMENT UNIT
PMU 1 VA CALIBRATION
ANGLE: 0.00°
PMU 1 VA CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 VB CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 VB CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 VC CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 VC CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 VX CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 VX CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 IA CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 IA CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 IB CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 IB CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 IC CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 IC CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 IG CALIBRATION
MESSAGE
ANGLE: 0.00°
PMU 1 IG CALIBRATION
MESSAGE
MAG: 100.0%
PMU 1 SEQ VOLT SHIFT
MESSAGE
ANGLE: 0°
PMU 1 SEQ CURR SHIFT
MESSAGE
ANGLE: 0°
N60 Network Stability and Synchrophasor Measurement System

PHASOR MEASUREMENT UNIT 1
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –180 to 180° in steps of 30
Range: –180 to 180° in steps of 30
5 SETTINGS

PMU 1 (to 4)
GE Multilin