B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 24 of 65)
ADDR
REGISTER NAME
47DF
Breaker 1 External Alarm
47E1
Breaker 1 Alarm Delay
47E3
Breaker 1 Pushbutton Control
47E4
Breaker 1 Manual Close Recall Time
47E6
Breaker 1 Out of Service
B
47E8
Breaker 1 Block Open
47EA
Breaker 1 Block Close
47EC
Breaker 1 Phase A / Three-pole Opened
47EE
Breaker 1 Phase B Opened
47F0
Breaker 1 Phase C Opened
47F2
Breaker 1 Operate Time
47F3
Breaker 1 Events
47F4
Reserved
47F5
...Repeated for Breaker 2
481A
...Repeated for Breaker 3
483F
...Repeated for Breaker 4
4864
...Repeated for Breaker 5
4889
...Repeated for Breaker 6
Demand (Read/Write Setting)
490A
Demand Current Method
490B
Demand Power Method
490C
Demand Interval
490D
Demand Input
Demand (Read/Write Command)
490F
Demand Clear Record
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
Field Unit Raw Data Actuals (Read Only) (8 modules)
4E00
Raw Field Data AC1 Mag
4E02
Raw Field Data AC1 Angle
4E03
Raw Field Data AC2 Mag
4E05
Raw Field Data AC2 Angle
4E06
Raw Field Data AC3 Mag
B-32
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 4294967295
---
0 to 65.535
s
0 to 1
---
0 to 65.535
s
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 65.535
s
0 to 1
---
0 to 65535
s
0 to 2
---
0 to 2
---
0 to 5
---
0 to 4294967295
---
0 to 1
---
0 to 65535
---
---
---
---
---
0 to 65535
---
---
---
0 to 0.001
A
0 to 0.1
degree
0 to 0.001
A
0 to 0.1
degree
0 to 0.001
A
APPENDIX B
STEP
FORMAT
DEFAULT
1
F300
0
0.001
F003
0
1
F102
0 (Disabled)
0.001
F003
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
0.001
F001
70
1
F102
0 (Disabled)
1
F001
0
1
F139
0 (Thermal
Exponential)
1
F139
0 (Thermal
Exponential)
1
F132
2 (15 MIN)
1
F300
0
1
F126
0 (No)
1
F001
0
---
F202
" "
---
F202
" "
1
F001
0
---
F001
0
0.001
F003
0
0.1
F002
0
0.001
F003
0
0.1
F002
0
0.001
F003
0
GE Multilin