GE N60 Instruction Manual page 450

Ur series network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 65)
ADDR
REGISTER NAME
1E20
...Repeated for Source 3
1E30
...Repeated for Source 4
1E40
...Repeated for Source 5
1E50
...Repeated for Source 6
Source Demand Peaks (Read Only Non-Volatile) (6 modules)
B
1E80
Source 1 Demand Ia Maximum
1E82
Source 1 Demand Ia Maximum Date
1E84
Source 1 Demand Ib Maximum
1E86
Source 1 Demand Ib Maximum Date
1E88
Source 1 Demand Ic Maximum
1E8A
Source 1 Demand Ic Maximum Date
1E8C
Source 1 Demand Watt Maximum
1E8E
Source 1 Demand Watt Maximum Date
1E90
Source 1 Demand Var
1E92
Source 1 Demand Var Maximum Date
1E94
Source 1 Demand Va Maximum
1E96
Source 1 Demand Va Maximum Date
1E98
Reserved (8 items)
1EA0
...Repeated for Source 2
1EC0
...Repeated for Source 3
1EE0
...Repeated for Source 4
1F00
...Repeated for Source 5
1F20
...Repeated for Source 6
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
Synchrocheck Actual Values (Read Only) (4 modules)
2400
Synchrocheck 1 Delta Voltage
2402
Synchrocheck 1 Delta Frequency
2403
Synchrocheck 1 Delta Phase
2404
...Repeated for Synchrocheck 2
2408
...Repeated for Synchrocheck 3
240C
...Repeated for Synchrocheck 4
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
2461
Field Raw Data Freeze
Phasor Measurement Unit Actual Values (Read Only) (4 modules)
2540
PMU 1 Phase A Voltage Magnitude
2542
PMU Unit 1 Phase A Voltage Angle
2543
PMU 1 Phase B Voltage Magnitude
2545
PMU 1 Phase B Voltage Angle
2546
PMU 1 Phase C Voltage Magnitude
2548
PMU 1 Phase C Voltage Angle
2549
PMU 1 Auxiliary Voltage Magnitude
254B
PMU 1 Auxiliary Voltage Angle
254C
PMU 1 Positive Sequence Voltage Magnitude
254E
PMU 1 Positive Sequence Voltage Angle
254F
PMU 1 Negative Sequence Voltage Magnitude
2551
PMU 1 Negative Sequence Voltage Angle
2552
PMU 1 Zero Sequence Voltage Magnitude
2554
PMU 1 Zero Sequence Voltage Angle
2555
PMU 1 Phase A Current Magnitude
2557
PMU 1 Phase A Current Angle
2558
PMU 1 Phase B Current Magnitude
B-16
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 999999.999
A
0 to 4294967295
---
0 to 999999.999
A
0 to 4294967295
---
0 to 999999.999
A
0 to 4294967295
---
0 to 999999.999
W
0 to 4294967295
---
0 to 999999.999
var
0 to 4294967295
---
0 to 999999.999
VA
0 to 4294967295
---
---
---
0 to 1
---
-1000000000000 to
V
1000000000000
0 to 655.35
Hz
0 to 359.9
degrees
0 to 7
---
0 to 1
---
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
V
-180 to 180
°
0 to 999999.999
A
-180 to 180
°
0 to 999999.999
A
APPENDIX B
STEP
FORMAT
DEFAULT
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
---
F001
0
1
F126
0 (No)
1
F060
0
0.01
F001
0
0.1
F001
0
1
F244
6 (H1a)
1
F102
0 (Disabled)
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
0.1
F002
0
0.001
F060
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents