5 SETTINGS
Select the
DIRECT I/O DATA RATE
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communica-
tions cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately
0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each 'bridge'.
Table 5–9: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
74
Channel 1
Channel 2
7L
Channel 1
Channel 2
7M
Channel 1
Channel 2
7P
Channel 1
Channel 2
7T
Channel 1
7W
Channel 1
Channel 2
7V
Channel 1
Channel 2
2A
Channel 1
2B
Channel 1
Channel 2
2G
Channel 1
2H
Channel 1
76
Channel 1
77
Channel 1
Channel 2
75
Channel 1
Channel 2
7E
Channel 1
Channel 2
7F
Channel 1
Channel 2
7G
Channel 1
Channel 2
7Q
Channel 1
Channel 2
7R
Channel 1
7S
Channel 1
Channel 2
The G.703 modules are fixed at 64 kbps. The
NOTE
The
DIRECT I/O CHANNEL CROSSOVER
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the
Inputs and outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
to match the data capabilities of the communications channel. All IEDs communicating
SUPPORTED DATA RATES
64 kbps
64 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps
64 kbps
64 kbps
128 kbps
128 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
DIRECT I/O DATA RATE
setting applies to N60s with dual-channel communication cards and allows crossing
5.2 PRODUCT SETUP
setting is not applicable to these modules.