Advertisement

5.6 GROUPED ELEMENTS
c) PHASE OVERVOLTAGE (ANSI 59P, IEC PTOV)
5

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 OVERVOLTAGE1
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as
calculated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below.
5-166
Figure 5–64: PHASE UNDERVOLTAGE1 SCHEME LOGIC
SETTING GROUP 1(6)
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE OV1
MESSAGE
PICKUP: 1.000 pu
PHASE OV1 PICKUP
MESSAGE
DELAY:
PHASE OV1 RESET
MESSAGE
DELAY:
PHASE OV1 BLOCK:
MESSAGE
Off
PHASE OV1
MESSAGE
TARGET: Self-reset
PHASE OV1
MESSAGE
EVENTS: Disabled
N60 Network Stability and Synchrophasor Measurement System

VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: FlexLogic Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS

PHASE OVERVOLTAGE1