2.1 INTRODUCTION
An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that
is centrally managed, enables user attribution, provides accounting of all user activities, and uses secure standards-
based strong cryptography for authentication and credential protection.
A Role-Based Access Control (RBAC) system that provides a permission model that allows access to UR device oper-
ations and configurations based on specific roles and individual user accounts configured on the AAA server (that is,
Administrator, Supervisor, Engineer, Operator, Observer).
2
Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM)
systems for centralized cybersecurity monitoring.
Strong encryption of all access and configuration network messages between the EnerVista software and UR devices
using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter
Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the
National Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems.
Example: Administrative functions can be segmented away from common operator functions, or engineering type access,
all of which are defined by separate roles, as shown in the following figure, so that access of UR devices by multiple per-
sonnel within a substation is allowed. Permission for each role are outlined in the next section.
There are two types of authentication supported by CyberSentry that can be used to access the UR device:
Device Authentication (local UR device authenticates)
Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attribut-
able.
In cases where user attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.
CYBERSENTRY USER ROLES
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user's logged in
role.
Example: Observer cannot write any settings.
The table lists the roles that are supported and their corresponding capabilities.
2-4
Figure 2–2: CYBERSENTRY USER ROLES
N60 Network Stability and Synchrophasor Measurement System