Hitachi WJ200-004M Quick Reference Manual page 51

Wj200 series
Hide thumbs Also See for WJ200-004M:
Table of Contents

Advertisement

Func.
Name
Code
PID sleep function action
a156
threshold
PID sleep function action delay
a157
time
[VR] input active range start
A161
frequency
[VR] input active range end
A162
frequency
A163
[VR] input active range start %
A164
[VR] input active range end %
[VR] input start frequency
A165
select
"A" Function
Description
Sets the threshold for the action,
set range 0.0~400.0 Hz
Sets the delay time for
the action, set range
0.0~25.5 sec
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the
current input range,
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A161 value)
01...Use 0Hz
50
Run
Defaults
Mode
Initial data
Units
Edit
0.00
0.0
sec.
0.00
0.00
0.
100.
01
Hz
Hz
Hz
%
%

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wj200-007m

Table of Contents