Download Print this page

Hitachi WJ200-004M Quick Reference Manual page 10

Wj200 series
Hide thumbs

Advertisement

Wire the Inverter Input to a Supply
In this step, you will connect wiring to the input of the inverter. This Inverter is single-phase
power only. The power connection terminals are [L1] and [N]. So you must refer to the
specifications label (on the side of the inverter) for the acceptable power source
types! Single-phase inverter models will have no connection to the [S/L2] terminal.
This is only used for three-phase models. Note the use of ring lug connectors is
recommended for a secure connection.
Single-phase 100V 0.4kW
Single-phase 100V 0.75kW
NOTE: An inverter powered by a portable power generator may cause a distorted power
waveform, overheating the generator. In general, the generator capacity should be five
times that of the inverter (kVA).
Chassis Ground (M4)
Chassis Ground (M4)
9
Single-phase
RB
P/+
L1
N U/T1 V/T2 W/T3
Power input
Output to Motor
Single-phase
RB
P/+ -
L1
N U/T1 V/T2 W/T3
Power input
Output to Motor
-

Advertisement

loading

  Related Manuals for Hitachi WJ200-004M

This manual is also suitable for:

Wj200-007m