Hitachi WJ200-004M Quick Reference Manual page 67

Wj200 series
Hide thumbs

Advertisement

Option
Terminal
Code
Symbol
UDC
Remote Control Data
29
Clearing
OPE
Operator Control
31
SF1
Multi-speed Select,
32
Bit operation Bit 1
SF2
Multi-speed Select,
33
Bit operation Bit 2
SF3
Multi-speed Select,
34
Bit operation Bit 3
SF4
Multi-speed Select,
35
Bit operation Bit 4
SF5
Multi-speed Select,
36
Bit operation Bit 5
SF6
Multi-speed Select,
37
Bit operation Bit 6
SF7
Multi-speed Select,
38
Bit operation Bit 7
OLR
Overload Restriction
39
Source Changeover
TL
Torque Limit Selection
40
TRQ1
Torque limit switch 1
41
TRQ2
Torque limit switch 2
42
BOK
Brake confirmation
44
LAC
LAD cancellation
46
PCLR
Pulse counter clear
47
ADD
ADD frequency enable
50
F-TM
Force Terminal Mode
51
ATR
Enable torque
52
command input
KHC
Clear watt-hour data
53
MI1
General purpose input
56
(1)
MI2
General purpose input
57
(2)
Input Function Summary Table
Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Description
Clears the UP/DWN frequency memory by forcing it to
equal the set frequency parameter F001. Setting C101
must be set=00 to enable this function to work
UP/DWN frequency memory is not changed
Forces the source of the output frequency setting A001
and the source of the Run command A002 to be from
the digital operator
Source of output frequency set by A001 and source of
Run command set by A002 is used
Bit encoded speed select, Bit 1, logical 1
Bit encoded speed select, Bit 1, logical 0
Bit encoded speed select, Bit 2, logical 1
Bit encoded speed select, Bit 2, logical 0
Bit encoded speed select, Bit 3, logical 1
Bit encoded speed select, Bit 3, logical 0
Bit encoded speed select, Bit 4, logical 1
Bit encoded speed select, Bit 4, logical 0
Bit encoded speed select, Bit 5, logical 1
Bit encoded speed select, Bit 5, logical 0
Bit encoded speed select, Bit 6, logical 1
Bit encoded speed select, Bit 6, logical 0
Bit encoded speed select, Bit 7, logical 1
Bit encoded speed select, Bit 7, logical 0
Perform overload restriction
Normal operation
Setting of b040 is enabled
Max. torque is limited with 200%
Torque limit related parameters of Powering/regen, and
FW/RV modes are selected by the combinations of
these inputs.
Brake wait time (b124) is valid
Brake wait time (b124) is not valid
Set ramp times are ignored. Inverter output
immediately follows the freq. command.
Accel. and/or decel. is according to the
set ramp time
Clear the position deviation data
Maintain the position deviation data
Adds the A145 (add frequency) value
to the output frequency
Does not add the A145 value to the
output frequency
Force inverter to use input terminals
for output frequency and Run command sources
Source of output frequency set by A001 and source of
Run command set by A002 is used
Torque control command input is enabled
Torque control command input is disabled
Clear watt-hour data
No action
General purpose input (1) is made ON under EzSQ
General purpose input (1) is made OFF under EzSQ
General purpose input (2) is made ON under EzSQ
General purpose input (2) is made OFF under EzSQ
66