Hitachi WJ200-004M Quick Reference Manual page 55

Wj200 series
Hide thumbs

Advertisement

Func.
Name
Code
Function code display
b037
restriction
b038
Initial display selection
Automatic user parameter
B039
registration
B040
Torque limit selection
B041
Torque limit 1 (fwd/power)
b042
Torque limit 2 (rev/power)
B043
Torque limit 3 (rev/power)
B044
Torque limit 4 (fwd/regen.)
b045
Torque LAD STOP selection
b046
Reverse run protection
b049
Dual Rating Selection
Controlled deceleration on
B050
power loss
DC bus voltage trigger level of
B051
ctrl. decel.
Over-voltage threshold of ctrl.
B052
decel.
B053
Deceleration time of ctrl. decel.
"b" Function
Description
Seven option codes:
00...Full display
01...Function-specific display
02...User setting (and b037)
03...Data comparison display
04...Basic display
05...Monitor display only
000...Func. code that SET key
pressed last displayed.(*)
001~030...d001~d030 displayed
201...F001 displayed
202...B display of LCD operator
Two option codes:
00...Disable
01...Enable
Four option codes:
00...Quadrant-specific setting mode
01...Terminal-switching mode
02...Analog voltage input mode(O)
Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
Torque limit level in reverse
powering quadrant, range is 0 to
200%/no(disabled)
Torque limit level in forward regen.
quadrant, range is 0 to
200%/no(disabled)
Two option codes:
00...Disable
01...Enable
Two option codes:
00...No protection
01...Reverse rotation is protected
It is not possible to change.
Four option codes:
00...Trips
01...Decelerates to a stop
02...Decelerates to a stop with DC
bus voltage controlled
03...Decelerates to a stop with DC
bus voltage controlled,
then restart
Setting of DC bus voltage to start
controlled decel. operation. Range is
0.0 to 1000.0
Setting the OV-LAD stop level of
controlled decel. operation. Range is
0.0 to 1000.0
Range is 0.01 to 3600.0
54
Run
Defaults
Mode
Initial data
Units
Edit
04
001
00
00
200
%
200
%
200
%
200
%
00
01
00
00
220.0
V
360.0
V
1.0
sec.