Func.
Name
Code
A092
Acceleration time (2)
Acceleration time (2),
A292
nd
2
motor
A093
Deceleration time (2)
Deceleration time (2),
A293
nd
2
motor
Select method to switch to
A094
Acc2/Dec2 profile
Select method to switch to
A294
Acc2/Dec2 profile, 2
Acc1 to Acc2 frequency
A095
transition point
Acc1 to Acc2 frequency
A295
transition point, 2
Dec1 to Dec2 frequency
A096
transition point
Dec1 to Dec2 frequency
A296
transition point, 2
A097
Acceleration curve selection
A098
Deceleration curve selection
[OI] input active range start
A101
frequency
[OI] input active range end
A102
frequency
[OI] input active range start
A103
current
[OI] input active range end
A104
current
[OI] input start frequency
A105
select
"A" Function
Duration of 2
acceleration, range is:
0.01 to 3600 sec.
Duration of 2
deceleration, range is:
0.01 to 3600 sec.
Three options for switching from
1st to 2nd accel/decel:
00
...2CH input from terminal
01
...Transition frequency
nd
motor
02
...Forward and reverse
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
nd
motor
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
nd
motor
Set the characteristic curve of
Acc1 and Acc2, five options:
00...linear
01...S-curve
02...U-curve
03...Inverse U-curve
04...EL S-curve
Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the
current input range,
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A101 value)
01...Use 0Hz
Description
nd
segment of
nd
segment of
48
Run
Defaults
Mode
Initial data
Units
Edit
10.00
sec.
10.00
sec.
10.00
sec.
10.00
sec.
00
00
0.0
0.0
0.0
0.0
01
01
0.00
0.0
20.
100.
00
Hz
Hz
Hz
Hz
Hz
Hz
%
%

Advertisement