Download Print this page

Hitachi WJ200-004M Quick Reference Manual page 61

Wj200 series
Hide thumbs

Advertisement

Func.
Name
Code
[AM] terminal selection
C028
(Analog voltage output
0...10V)
Digital current monitor
C030
reference value
C031
Output [11] active state
C032
Output [12] active state
C036
Alarm relay active state
Output mode of low current
C038
detection
C039
Low current detection level
Output mode of overload
C040
warning
C041
Overload warning level
Overload warning level, 2
C241
motor
Frequency arrival setting
C042
for acceleration
Frequency arrival setting
C043
for deceleration
C044
PID deviation level
Frequency arrival setting 2
C045
for acceleration
Frequency arrival setting 2
C046
for deceleration
"C" Function
Description
11 programmable functions:
00...Output frequency
01...Output current
02...Output torque
04...Output voltage
05...Input power
06...Electronic thermal load ratio
07...LAD frequency
10...Heat sink temperature
11...Output torque (with code)
13...General output
16...Option
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
00...normally open [NO]
01...normally closed [NC]
Two option codes:
00...During acceleration,
deceleration and constant speed
01...During constant speed only
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
Two option codes:
00...During accel., decel. And
constant speed
01...During constant speed only
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Sets the overload warning signal
nd
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
Set range is 0.0 to 400.0 Hz
Set range is 0.0 to 400.0 Hz
60
Run
Defaults
Mode
Initial data
Edit
07
[LAD]
Rated
current
00
00
01
01
INV rated
current
01
Rated current
x 1.15
Rated current
x 1.15
0.0
0.0
3.0
0.00
0.00
Units
A
A
A
A
Hz
Hz
%
Hz
Hz

Advertisement