Hitachi WJ200-004M Quick Reference Manual page 58

Wj200 series
Hide thumbs Also See for WJ200-004M:
Table of Contents

Advertisement

Func.
Name
Code
b096
BRD activation level
b097
BRD resistor value
B100
Free V/F setting, freq.1
b101
Free V/F setting, voltage.1
b102
Free V/F setting, freq.2
b103
Free V/F setting, voltage.2
b104
Free V/F setting, freq.3
b105
Free V/F setting, voltage.3
b106
Free V/F setting, freq.4
b107
Free V/F setting, voltage.4
b108
Free V/F setting, freq.5
b109
Free V/F setting, voltage.5
b110
Free V/F setting, freq.6
b111
Free V/F setting, voltage.6
b112
Free V/F setting, freq.7
b113
Free V/F setting, voltage.7
B120
Brake control enable
b121
Brake Wait Time for Release
Brake Wait Time for
b122
Acceleration
b123
Brake Wait Time for Stopping
Brake Wait Time for
b124
Confirmation
b125
Brake release freq.
b126
Brake release current
b127
Braking freq. setting
Deceleration overvoltage
B130
suppression enable
B131
Decel. overvolt. suppress level
Decel. overvolt. Suppress
b132
const.
Decel. overvolt. Suppress
B133
proportional gain
"b" Function
Description
Range is:
330 to 380V (200V class)
Min.Resistance to 600.0
Set range, 0 ~ value of b102
Set range, 0 ~ 800V
Set range, value of b100 ~b104
Set range, 0 ~ 800V
Set range, value of b102 ~b106
Set range, 0 ~ 800V
Set range, value of b104 ~b108
Set range, 0 ~ 800V
Set range, value of b108 ~b110
Set range, 0 ~ 800V
Set range, value of b108 ~b112
Set range, 0 ~ 800V
Set range, b110 ~ 400
Set range, 0 ~ 800V
Two option codes:
00...Disable
01...Enable
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0 to 400Hz
Set range: 0~200% of inverter rated
current
Set range: 0 to 400Hz
00...Disabled
01...Enabled
02...Enabled with accel.
DC bus voltage of suppression.
Range is:
200V class...330 to 395
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 sec.
Proportional gain when b130=01.
Range is: 0.00 to 5.00
57
Run
Defaults
Mode
Initial data
Units
Edit
360
V
Min.
Ohm
Resistance
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
00
0.00
sec.
0.00
sec.
0.00
sec.
0.00
sec.
0.00
sec.
(rated
A
current)
0.00
Hz
00
380
V
1.00
sec.
0.20

Advertisement