Hitachi WJ200-004M Quick Reference Manual page 57

Wj200 series
Hide thumbs

Advertisement

Func.
Name
Code
B087
STOP key enable
B088
Restart mode after FRS
Automatic carrier frequency
b089
reduction
b090
Dynamic braking usage ratio
B091
Stop mode selection
B092
Cooling fan control
Clear elapsed time of cooling
B093
fan
b094
Initialization target data
Dynamic braking control
b095
(BRD) selection
"b" Function
Description
Select whether the STOP key on the
keypad is enabled, three option
codes:
00...Enabled
01...Disabled always
02... Disabled for stop
Selects how the inverter resumes
operation when free-run stop (FRS)
is cancelled, three options:
00...Restart from 0Hz
01...Restart from frequency
detected from real speed of
motor (freq. matching)
02...Restart from frequency
detected from real speed of
motor (active freq. matching)
Three option codes:
00...Disabled
01...Enabled, depending on the
output current
02...Enabled, depending on the
heat-sink temperature
Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
Select how the inverter stops the
motor, two option codes:
00...DEC (decelerate to stop)
01...FRS (free-run to stop)
Selects when the fan is ON during
inverter operation, four options:
00...Fan is always ON
01...Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02...Fan is temperature controlled
Two option codes:
00...Count
01...Clear
Select initialized parameters, four
option codes:
00...All parameters
01...All parameters except in/output
terminals and communication.
02...Only registered parameters
in Uxxx.
03...All parameters except
registered parameters in Uxxx
and b037.
Three option codes:
00...Disable
01...Enable during run only
02...Enable always
56
Run
Defaults
Mode
Initial data
Units
Edit
00
00
01
0.0
%
00
01
00
00
01