CHAPTER 5: SETTINGS
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.7.3 Line differential elements
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL ELEMENTS
LINE DIFFERENTIAL
ELEMENTS
5.7.3.1 Current differential
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL... CURRENT DIFFERENTIAL
CURRENT
DIFFERENTIAL
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
NEUTRAL CURRENT
GROUND CURRENT
NEGATIVE SEQUENCE
CURRENT
BREAKER FAILURE
VOLTAGE ELEMENTS
SUPERVISING
ELEMENTS
CURRENT
DIFFERENTIAL
STUB BUS
CURRENT DIFF
FUNCTION: Disabled
CURRENT DIFF SIGNAL
SOURCE 1: SRC 1
CURRENT DIFF BLOCK:
Off
CURRENT DIFF
PICKUP: 0.20 pu
CURRENT DIFF
CT TAP 1: 1.00
CURRENT DIFF
CT TAP 2: 1.00
CURRENT DIFF
RESTRAINT 1: 30%
CURRENT DIFF
RESTRAINT 2: 50%
CURRENT DIFF
BREAK PT: 1.0 pu
INRUSH INHIBIT MODE:
Disabled
GROUPED ELEMENTS
See page 5-226
See page 5-234
See page 5-237
See page 5-239
See page 5-249
See page 5-256
See below
See page 5-213
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: FlexLogic operand
Range: 0.10 to 4.00 pu in steps of 0.01
Range: 0.20 to 5.00 in steps of 0.01
Range: 0.20 to 5.00 in steps of 0.01
Range: 1 to 50% in steps of 1
Range: 1 to 70% in steps of 1
Range: 0.0 to 20.0 pu in steps of 0.1
Range: Disabled, Per phase, 2-out-of-3, Average
5