GE L30 Instruction Manual page 266

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

PRODUCT SETUP
Table 5-9: Port and protocol combinations
PROTOCOL
DNP CHANNEL 1(2) PORT
setting
settings
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Channel 1: Eth TCP
Channel 2: none
Channel 1: none
Channel 2: Eth TCP
Channel 1: Eth UDP
Channel 2: none
Channel 1: Eth TCP
Channel 2: RS485
Channel 1: Eth TCP
Channel 2: RS232
Channel 1: Eth UDP
Channel 2: RS485
Channel 1: Eth UDP
Channel 2: RS232
Channel 1: RS485
Channel 2: Eth TCP
Channel 1: RS232
Channel 2: Eth TCP
Channel 1: RS485
Channel 2: RS232
5
Channel 1: RS232
Channel 2: RS485
Channel 1: RS485
Channel 2: none
IEC 104
IEC 103
5.3.5.10 DNP protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL
 DNP PROTOCOL
5-52
RS232
RS485
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
DNP
DNP
Modbus
Modbus
DNP
DNP
Modbus
Modbus
DNP
DNP
Modbus
DNP
DNP
DNP
DNP
Modbus
DNP
Modbus
Modbus
Modbus
IEC 103
 DNP CHANNELS
DNP ADDRESS:
1
 DNP NETWORK
 CLIENT ADDRESSES
DNP TCP/UDP PORT
NUMBER(20000): 20000
DNP UNSOL RESPONSE
FUNCTION: Disabled
DNP UNSOL RESPONSE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MAX RETRIES: 10
DNP UNSOL RESPONSE
DEST ADDRESS: 1
DNP CURRENT SCALE
FACTOR: 1
Ethernet
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
Modbus, IEC 61850
Modbus, IEC 61850
Modbus, IEC 61850
IEC 104, Modbus, IEC 61850
Modbus, IEC 61850
See below
Range: 0 to 65535 in steps of 1
See below
Range: 0 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 60 s in steps of 1
Range: 1 to 255 in steps of 1
Range: 0 to 65519 in steps of 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL