CHAPTER 5: SETTINGS
Table 5-20: FlexLogic operands supported by aggregator
Operand type
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
as above
as above
as above
as above
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1  90-5 AGGR 1
CONFIGURATION
 90-5 AGGR 1
 CONFIGURATION
— A user-defined visible string of characters (maximum 56) to identify the source of the stream.
PMU AGGREGATOR 1 NAME
This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850
MSVID filed in the output stream. The field allows 65 characters, but uses the first 56 characters.
AGGREGATOR 1: PHYSICAL PORT
transmitted. The range is 1, 2, 3.
PMU AGGREGATOR 1: UDP PORT
A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR 1: NUMBER OF ASDUs
through to 4.
Table 5-21: Number of ASDUs
Settings for
Transmission
ASDU
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Operand syntax
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
PMU AGGREGATOR 1
NAME:
PMU AGGREGATOR 1
PORT: 1
PMU AGGREGATOR 1
UDP PORT: 102
PMU AGGREGATOR 1
NUMBER OF ASDUs: 1
— This setting determines the physical ports through which the synchrophasor traffic is
— This setting selects the UDP port number that is used by this dataset for network reporting.
— This setting sets the number of Application Service Data Units (ASDUs) from 1
Operand description
Phasor data concentrator asserts control bit 1, as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Range: 56-character ASCII text (blank by default)
Range: 1, 2, 3
Range: 0 to 65534 in steps of 1
Range: 1 to 4
SYSTEM SETUP
5
5-183