SYSTEM SETUP
Each Phasor Measurement Unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated PMU
recorder, or cross-triggering of other PMUs in the system. They are
Overfrequency and underfrequency
Overvoltage and undervoltage
Overcurrent
Overpower
High rate of change of frequency
The pre-configured triggers can be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
5
The trigger reset (drop-off) timer is available for all five triggering functions (FREQ, ROCOF, VOLT, CURR, POWER) in individual
trigger settings under the
operand with stat bits 3 and 11 for a fixed interval defined by this setting. If it is required that
stat bits 3 and 11 stay longer than the individual reset timer, then use the
appropriate elements and FlexLogic. In short, in case of
FlexLogic.
5.5.8.12 User triggering
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 USER TRIGGER
 PMU 1 USER
 TRIGGER
The user trigger allows customized triggering logic to be constructed from FlexLogic. The entire triggering logic is refreshed
every two power system cycles.
5.5.8.13 Frequency triggering
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 FREQUENCY TRIGGER
 PMU 1 FREQUENCY
 TRIGGER
5-176
Figure 5-88: STAT bits logic
setting. This asserts individual trigger operand and overall
TRIGGER DPO TIME
PMU 1 USER TRIGGER:
Off
PMU 1 FREQ TRIGGER
FUNCTION: Disabled
PMU 1 FREQ TRIGGER
LOW-FREQ: 49.00 Hz
PMU 1 FREQ TRIGGER
HIGH-FREQ: 61.00 Hz
PMU x USER TRIGGER
, the drop-off time needs to be implemented using
USER TRIGGER
Range: FlexLogic operand
Range: Enabled, Disabled
Range: 20.00 to 70.00 Hz in steps of 0.01
Range: 20.00 to 70.00 Hz in steps of 0.01
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
PMU x TRIGGERED
operand with
PMU x TRIGGERED
setting assigned with