COMMANDS MENU

7.1.1 Virtual inputs

COMMANDS  VIRTUAL INPUTS
 COMMANDS
 VIRTUAL INPUTS
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status is a state off (logic 0) or on (logic 1).

7.1.2 Clear records

COMMANDS  CLEAR RECORDS
 COMMANDS
 CLEAR RECORDS
7
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to "Yes" and pressing the
"No."
7-2
Virt Ip 1
Off
Virt Ip 2
Off
Virt Ip 64
Off
CLEAR FAULT REPORTS?
No
CLEAR EVENT RECORDS?
No
CLEAR OSCILLOGRAPHY?
No
CLEAR DATA LOGGER?
No
CLEAR BREAKER 1
ARCING AMPS? No
CLEAR BREAKER 2
ARCING AMPS? No
CLEAR CHANNEL TEST
RECORDS? No
CLEAR UNAUTHORIZED
ACCESS? No
CLEAR PMU 1 RECORDS?
No
CLEAR PMU 1 CONFIG
CHANGE COUNTER? No
CLEAR INCIPIENT
FAULT COUNTERS? No
 CLEAR IEC61850
 XWSI OPCNT
 CLEAR IEC61850
 XCBR OPCNT
CLEAR ALL RELAY
RECORDS? No
key. After clearing data, the command setting automatically reverts to
ENTER
CHAPTER 7: COMMANDS AND TARGETS
Range: Off, On
Range: Off, On
Range: Off, On
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
See below
See below
Range: No, Yes
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL