CHAPTER 5: SETTINGS
Configure
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual." The window configures metering
values.
Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the metering window. A
FlexAnalog is an analog parameter.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply, for example with RxGOOSE Analogs.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed metered value. It can be used to provide for leading
character spacing of the display value.
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-10: Metering value properties window
PRODUCT SETUP
5
5-35