Pmu Aggregator; Transducer Inputs And Outputs - GE L30 Instruction Manual

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

METERING
These actual values display without the corresponding time stamp as they become available per the recording rate
6
setting. Also, the recording post-filtering setting is applied to these values.

6.4.10 PMU aggregator

ACTUAL VALUES  METERING  PHASOR MEASURMENT UNIT  PMU AGGREGATOR 1
 PMU AGGREGATOR 1
Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernet
frame size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown in
the displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result in
fragmented data frames, causing increased network traffic.

6.4.11 Transducer inputs and outputs

ACTUAL VALUES  METERING  TRANSDUCER I/O DCMA INPUTS  DCMA INPUT xx
 DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
6-24
PMU 1 V1:
0.000 V
0.00°
PMU 1 V2:
0.000 V
0.00°
PMU 1 V0:
0.000 V
0.00°
PMU 1 IA:
0.000 A
0.00°
PMU 1 IB:
0.000 A
0.00°
PMU 1 IC:
0.000 A
0.00°
PMU 1 IG:
0.000 A
0.00°
PMU 1 I1:
0.000 A
0.00°
PMU 1 I2:
0.000 A
0.00°
PMU 1 I0:
0.000 A
0.00°
PMU 1 FREQUENCY:
0.000 Hz
PMU 1 df/dt:
0.00 Hz/s
PMU 1 CONFIG CHANGE
COUNTER:
PMU AGGREGATOR 1
PDU SIZE: 0
DCMA INPUT xx
0.000 mA
Range: Substituted with zero if delta-connected VTs
Range: 0 to 65535
0
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES