Diagnostic Messages - Emerson Rosemount 3051P Reference Manual

In-line pressure, with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Reference Manual
00809-0700-4001, Rev AA
6.3

Diagnostic messages

Listed in the below sections are detailed table of the possible messages that will appear on either the
LCD/LOI display, a Field Communicator, or an AMS Device Manager system. Use the tables below to
diagnose particular status messages.
Good
Failed – fix now
Maintenance – fix soon
Advisory
Table 6-2. Status: Failed – Fix Now
LCD display
Alert name
screen
NO P
No Pressure
UPDATE
Updates
FAIL
Electronics
BOARD
Board Failure
Critical
Sensor Data
Error
MEMRY
ERROR
Critical
Electronics
Data Error
FAIL
Sensor Failure
SENSOR
Incompatible
XMTR
Electronics
MSMTCH
and Sensor
Table 6-3. Status: Maintenance – Fix Soon
LCD
Alert name
display
screen
No
NO T
Temperature
UPDATE
Updates
PRES
Pressure Out
LIMITS
of Limits
Troubleshooting
LOI screen
NO PRESS
There are no pressure updates
UPDATE
from the sensor to the electronics
FAIL
A failure has been detected in the
BOARD
electronics circuit board
A user written parameter does not
match the expected value
MEMORY
ERROR
A user written parameter does not
match the expected value
FAIL
A failure has been detected in the
SENSOR
pressure sensor
XMTR
The pressure sensor is
MSMTCH
incompatible with the attached
LOI screen
Problem
There are no temperature
NO TEMP
updates from the sensor to
UPDATE
the electronics
PRES OUT
The pressure is either above
LIMITS
or below the sensor limits
Problem
electronics
1. Ensure the sensor cable connection to the
electronics is tight.
2. Replace the pressure transmitter.
1. Check the transmitter pressure connection to
ensure it is not plugged or the isolating
diaphragms are not damaged.
2. Replace the pressure transmitter.
Troubleshooting
Recommended action
1. Ensure the sensor cable connection to the
electronics is tight.
2. Replace the transmitter.
1. Replace the pressure transmitter.
1. Confirm and correct all parameters listed
in Device Information.
2. Perform a Device Reset.
3. Replace Pressure Transmitter.
1. Confirm and correct all parameters listed
in Device Information.
2. Perform a Device Reset.
3. Replace pressure transmitter.
1. Replace pressure transmitter.
1. Replace the pressure transmitter.
Recommended action
May 2017
59