Changing A Transmitter Address; Communicating With A Multidropped Transmitter - Emerson Rosemount 3051P Reference Manual

In-line pressure, with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Reference Manual
00809-0700-4001, Rev AA
2.13.1

Changing a transmitter address

To activate multidrop communication, the transmitter poll address must be assigned a number from 1
to 15 for HART Revision 5, and 1–63 for HART Revision 7. Each transmitter in a multidropped loop must
have a unique poll address.
Changing transmitter address using a Field Communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Changing transmitter address using AMS Device Manager
1. Right click the device and select Configure.
2. In HART Revision 5 mode:
a. Select Manual Setup, select the HART tab.
b. In the Communication Settings box enter polling address in the Polling Address box, select
3. In HART Revision 7 mode:
a. Select Manual Setup, select the HART tab and select the Change Polling Address button.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
2.13.2

Communicating with a multidropped transmitter

To communicate with a multidrop transmitter, the Field Communicator or AMS Device Manager has to
be set up for Polling.
Communicating with a multidropped transmitter using a Field
Communicator
1. Select Utility and Configure HART Application.
2. Select Polling Addresses.
3. Enter 0–63.
Communicating with a multidropped transmitter using AMS Device
Manager
1. Select the HART modem icon and select Scan All Devices.
Configuration
Send.
HART Revision 5
HART Revision 7
2, 2, 5, 2, 1
2, 2, 5, 2, 2