Configuration
May 2017
Note
If the transmitter security is on, adjustments to the zero and span will not be able to be made. Refer to
"Configuring transmitter security" on page 36
The span is maintained when the 4 mA/1 V point is set. The span changes when the 20mA 5 V point is
set. If the lower range point is set to a value that causes the upper range point to exceed the sensor
limit, the upper range point is automatically set to the sensor limit, and the span is adjusted
accordingly.
Regardless of the range points, the transmitter measure and report all readings within the digital
limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH
transmitter detects a pressure of 25 inH
range reading.
2.8.3

Damping

The damping command changes the response time of the transmitter; higher values can smooth
variations in output readings caused by rapid input changes. Determine the appropriate damping
setting based on the necessary response time, signal stability, and other requirements of the loop
dynamics within your system. The damping command utilizes floating point configuration allowing the
user to input any damping value within 0.0–60.0 seconds.
Damping with a Field Communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Enter desired Damping Value and select APPLY.
Damping with AMS Device Manager
1. Right click the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a LOI
Reference
Figure 2-11. Damping with LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
16
Figure 2-11
to enter damping values using an LOI.
EXTENDED MENU
CALIBRAT
DAMPING
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
for security information.
O, it digitally outputs the 25 inH
2
2, 2, 1, 1, 5
Reference Manual
00809-0700-4001, Rev AA
O, and the
2
O reading and a 250% of
2
Configuration