Product Certifications
May 2017

B.4 International

E7 IECEx Flameproof
Certificate: IECEx KEM 06.0021X
Standards: IEC 60079-0:2011, IEC 60079-1:2014, IEC
60079-26:2014
Markings: Ex db IIC T6...T4 Ga/Gb T6(–60 °C
°C), T5/T4(–60 °C
Table B-3. Process Connection Temperature
Temperature
Process connection
class
temperature
T6
–60 °C to +70 °C
T5
–60 °C to +80 °C
T4
–60 °C to +120 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1
mm thickness that forms a boundary between zone 0
(process connection) and zone 1 (all other parts of the
equipment). The model code and datasheet are to be
consulted for details of the diaphragm material.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from
electrostatic discharge. Avoid installations that could
cause electrostatic build-up on painted surfaces, and
only clean the painted surfaces with a damp cloth. If
paint is ordered through a special option code, contact
the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be
suitable for a temperature of 5°C greater than
maximum specified temperature for location where
installed.
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 12.0071X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (–55 °C
83
T
+70
a ≤
T
a ≤
+80 °C)
Ambient
temperature
–60 °C to +70 °C
–60 °C to +80 °C
–60 °C to +80 °C
T
+70 °C)
a ≤
Table B-4. Input Parameters
Parameter
Voltage U
i
Current I
i
Power P
i
Capacitance C
i
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal
block, the Model 3051P is incapable of passing the
500V isolation test. This must be taken into account
during installation.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however,
care should be taken to protect it from impact or
abrasion if located in a Zone 0 environment.
N7 IECEx Type n
Certificate: IECEx BAS 12.0072X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T5 Gc (-40 °C
Special Conditions for Safe Use (X):
1.
When fitted with a transient suppression terminal
block, the Model 2088 is incapable of passing the 500V
isolation test. This must be taken into account during
installation.
NK IECEx Dust
Certificate: IECEx BAS12.0073X
Standards: IEC60079-0:2011, IEC60079-31:2008
Markings: Ex t IIIC T50 °C T
Parameter
Voltage U
i
Current I
i
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable
blanking plugs which maintain the ingress protection
of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for
the ambient temperature range of the apparatus and
capable of withstanding a 7J impact test.
Reference Manual
00809-0700-4001, Rev AA
HART
30 V
200 mA
0.9 W
0.012 μF
T
a ≤
+70 °C)
60 °C Da
500
HART
36 V
24 mA
Product Certifications