Electrical Installations
May 2017
4.3

Local Operating Interface (LOI)/LCD display

Transmitters ordered with the LCD display option (M5) or LOI option (M4) are shipped with the display
installed. Installing the display on an existing transmitter requires a small instrument screwdriver.
Carefully align the desired display connector with the electronics board connector. If connectors don't
align, the display and electronics board are not compatible.
Figure 4-1. LOI Display Assembly
A. LCD/LOI display
B. Extended cover
C. Captive screws
4.3.1

Rotating LCD/LOI display

1. Secure the loop to manual control and remove power to transmitter.
2. Remove transmitter housing cover.
3. Remove screws form the LCD/LOI display and rotate to desired orientation.
a. Insert 10-pin connector into the display board for the correct orientation. Carefully align pins for
4. Re-insert screws.
5. Reattach transmitter housing cover; cover must be fully engaged to comply with explosion proof
requirements.
6. Re-attach power and return loop to automatic control.
4.4

Configuring transmitter security

There are four security methods with the Rosemount 3051P Transmitters.
Security switch
HART
Configuration Buttons lock
LOI password
36
C
insertion into the output board.
®
Lock
A
C
B
Reference Manual
00809-0700-4001, Rev AA