Switching Hart Revision With Ams Device Manager; Switching Hart Revision With Loi - Emerson Rosemount 3051P Reference Manual

In-line pressure, with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Reference Manual
00809-0700-4001, Rev AA
5.7.3

Switching HART revision with AMS Device Manager

1. Select Manual Setup and select HART.
2. Select Change HART Revision, then follow the on screen prompts.
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
5.7.4

Switching HART revision with LOI

Navigate to HART REV within the extended menu and select either HART REV 5 or HART REV 7. Use
Figure 5-8
Figure 5-8. Change HART Revision with LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Operation and Maintenance
below to change HART Revision.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
HART REV
BACK TO MENU
EXIT MENU
Operation and Maintenance
May 2017
55