Procedure
In the next step, in order to wire the ready signal of the infeed (terminal "DO: Ready" of the
infeed) with the DI 0 of the D4x5-2, proceed as follows in case you have not already established
the interconnection during processing using the drive wizard:
1. Navigate in the project navigator to the Drives folder and double-click Configuration below
the drive.
Figure 6-14
2. Click in the working area on the Configure DDS button with the yellow background.
Figure 6-15
The drive wizard opens.
3. Click Next in the drive wizard until you reach the dialog Configuration -
SINAMICS_Integrated - BICO power unit.
4. In the input field p0864, select the digital input (e.g. DI 0) to which the ready signal of the
infeed is wired.
Figure 6-16
SIMOTION SCOUT
Configuration Manual, 11/2016
Configuring a drive
Configuring DDS
BICO interconnection
Configuring/parameterizing
6.4 Configuring devices
95