Operating Modes - Samson TROVIS 5433 Mounting And Operating Instructions

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

Rotary switch for "Operating modes"
1.2

Operating modes

Day mode (rated operation)
Regardless of the programmed times-of-use and summer mode, the controller uses the set
points relevant for rated operation.
The DHW temperature set point remains constantly active in system Anl 6.
Night mode (reduced operation)
Regardless of the programmed times-of-use, the controller uses the set points relevant for re-
duced operation.
The Sustained DHW temperature remains constantly active in system Anl 6.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these
times-of-use, the controller is in reduced operation, unless control operation is deactivated
depending on the outdoor temperature. The controller switches automatically between both
operating modes.
Manual operation – 0 +
Valves and pumps can be controlled manually (–> section 3).
The default setting of the circulation pump is permanent operation.
Manual operation: valve closes
0
Manual operation: valve stationary
+
Manual operation: valve opens
Control operation deactivated, frost protection only
DHW heating active, heating switched off
Night mode (reduced operation)
Day mode (rated operation)
Automatic mode (operation according to time schedule)
Operation
7
EB 5433 EN