Setting The Times-Of-Use - Samson TROVIS 5433 Mounting And Operating Instructions

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

1.6

Setting the times-of-use

Three times-of-use can be set for each day of the week.
If a time-of-use is not required, its start and stop times must be set to identical times.
The times-of-use for heating and the DHW circulation pump are set using the top rotary
switch:
Times-of-use
Heating
DHW circulation pump
Parameters
Period/day
Start first time-of-use
Stop first time-of-use
Start second time-of-use
Stop second time-of-use
Start third time-of-use
Stop third time-of-use
*Default setting (WE) valid for heating (switch position
Note!
The times-of-use for DHW heating are set in parameter level PA2 similar to the times-of-use
for heating and the DHW circulation pump.
Position
WE*
Rotary switch / Range of values
1
1, 2, 3, 4, 5, 6, 7 with 1-7 = every day,
1 = Monday, 2 = Tuesday, ..., 7 = Sunday
7:00
0:00 h to 24:00 h; in steps of 30 minutes
22:00
0:00 h to 24:00 h; in steps of 30 minutes
22:00
0:00 h to 24:00 h; in steps of 30 minutes
22:00
0:00 h to 24:00 h; in steps of 30 minutes
22:00
0:00 h to 24:00 h; in steps of 30 minutes
22:00
0:00 h to 24:00 h; in steps of 30 minutes
)
Operation
11
EB 5433 EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents