Functions of the heating circuit
In rated operation, the heating is switched off when the room temperature exceeds the Day
set point by 2 °C. In reduced operation, the heating is switched off when the room tempera-
ture exceeds the Night set point by 2 °C.
Note!
We recommend not to select a cycle time that is too short. Cycle times that are too short have
a negative effect especially in case of cooling loads, such as drafts or open windows, that af-
fect the control process. Rooms may be temporarily overheated when the cooling load has
been eliminated!
Functions
Room sensor RS
Flash adaptation
Outdoor temperature t
48
EB 5433 EN
WE
0
0
10 min
1
A
Configuration
CO1 -> F01 - 1, option: 1
CO1 -> F03 - 1
Cycle time / 1 to 100 min
CO1 -> F07 - 0