Samson TROVIS 5433 Mounting And Operating Instructions page 78

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

Appendix
F Function
06 Summer mode
07 Outdoor
temperature t
A
08 Outdoor
temperature 0 to
10 V at input UE
09 Drying of jointless
floor
F Function block number, WE Default value, Anl System code number
78
EB 5433 EN
Comment
WE Anl
Function block parameters / Range of values (default)
0
All* CO1 -> F06 - 1: Time-controlled summer mode,
only with CO1 -> F07 - 1
Function block parameters:
Start summer mode / 01.01 to 31.12 (01.06)
No. of days until activation/ 1 to 3 (2)
Stop summer mode / 01.01 to 31.12 (30.09)
No. of days until deactivation / 1 to 3 (1)
OT limit value summer mode / 0 to 50 °C (18 °C)
1
All* CO1 -> F07 - 1: Weather-compensated control active
CO1 -> F07 - 0: Fixed set point control
Function block cannot be selected if:
CO1 -> F05 - 1 or CO1 -> F06 - 1 or CO1 -> F08 - 1 or
CO-SYS -> F12 - 1 or CO1 -> F02 - 1, options 1/2
0
All* CO1 -> F08 - 1: t
only with CO1 -> F07 - 1 and CO-SYS -> F11 - 0
CO1 -> F08 - 0: t
0
All* CO1 -> F09 - 1: Start the drying of jointless floor program only
by selecting START 1
Function block parameters:
Temperature rise / 1.0 to 10 °C / 24 h (5.0 °C / 24 h)
Maximum temperature / 25 to 60 °C (45 °C)
Maintaining time of maximum temperature / 1 to 10 days (4)
Temperature reduction / 0.0 to 10.0 °C / 24 h (5.0 °C/24 h)
Option: START 1
at input UE,
A
at input AS
A