reduced operating mode stops after the time for Activate priority in case of deviation has
elapsed.
Function
Priority through set-back
operation
6.8

Forced charging of the DHW storage tank

To provide the full room heating performance when the time-of-use of the heating circuits be-
gins, existing storage tanks are charged one hour before the time-of-use of the heating cir-
cuits starts. For the individual controller, this means that storage tank charging is activated
when the water temperature in the storage tank falls below the adjusted deactivation value of
T = DHW temperature + hysteresis . The forced charging of the storage tank does not occur
when the DHW circuit is not used at the beginning of the time-of-use set for the heating cir-
cuit.
Note! This function is not available when a storage tank thermostat is used.
6.9

Thermal disinfection of the DHW storage tank

In all systems with DHW storage tank, the DHW storage tank is thermally disinfected on a
selected Day of the week or every day.
The tank is heated up to the adjusted Disinfection temperature , taking into account the
Charging temperature boost . Disinfection begins at the adjusted Start time and, at the latest,
ends at the specified Stop time set in CO2 -> F20 - 0. In case of the Time-controlled thermal
disinfection (CO2 -> F20 - 1), the disinfection remains active even after the Disinfection tem-
perature is reached and ends at the adjusted Stop time .
In addition to this function or instead of it, the thermal disinfection can be activated by a bi-
nary input. The binary input, which initates the thermal disinfection process, functions either
as a momentary-action switch or a latching-action switch:
4
Functioning as a momentary-action swtich, the floating switch at input RS leads to the
next programmed thermal disinfection running right through from the Start time to the
Stop time .
4
Functioning as a latching-action switch, a closed contact of the floating switch at input RS
leads to the thermal disinfection being active until the contact is opened again.
blinks while the thermal disinfection is active.
WE
Configuration
0
CO2 -> F09 - 1, option: 2
300 sec
Activate priority in case of deviation / 60 to 600 sec
40 °C
Monitoring value / 20 to 90 °C
Functions of the DHW circuit
EB 5433 EN
57