Advertisement

Activation depending on outdoor temperature, deactivation depending on room temperature:
Optimization
Outdoor temperature t
Activation and deactivation depending on room temperature:
Optimization
Parameters
Day set point
Night set point
5.8

Flash adaptation

To achieve that the controller reacts immediately to room temperature deviations, set the
function block setting CO1 -> F03 - 1.
Flash adaptation counteracts room temperature deviations by increasing or decreasing the
flow temperature by up to 30 °C. The Cycle time determines the intervals at which the flow
temperature set point is corrected by 1 °C.
Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!
Functions
Room sensor RS
Flash adaptation
5.9

Room temperature dependent control

A Type 5244 or Type 5257-5 Room Panel needs to be connected for the room temperature
dependent control function; this control functions, however, without using an outdoor sensor.
The flow temperature is raised or reduced by up to 30 °C when room temperature deviations
occur. The cycle time determines the time between the correction of the flow temperature set
point by 1 °C. The flow temperature control starts with 50 °C as the set point, and 30 °C in
reduced operation, provided the Maximum flow temperature (PA1) permits it.
0
120 min
1
A
0
WE
20 °C
15 °C
WE
0
0
10 min
CO1 -> F02 - 1, option: 2
Advance heating time / 0 to 360 min
CO1 -> F07 - 1
CO1 -> F02 - 1, option: 3
Rotary switch / value range
10 to 40 °C
10 to 40 °C
Configuration
CO1 -> F01 - 1, option: 1
CO1 -> F03 - 1
Cycle time / 1 to 100 min
Functions of the heating circuit
EB 5433 EN
47