Appendix; Function Block Lists - Samson TROVIS 5433 Mounting And Operating Instructions

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

12

Appendix

12.1 Function block lists

CO1: Heating circuit (not system Anl 6)*
F Function
01 Room sensor RS
02 Optimization
03 Flash adaptation
04 Characteristic
05 Delayed outdoor
temperature
adaptation
Comment
WE Anl
Function block parameters / Range of values (default)
0
All* CO1 -> F01 - 1: Temperature display and input FG1 active;
Options:
Function block cannot be selected if
CO1 -> F02 - 1, options 2/3 or CO1 -> F03 - 1 or
CO1 -> F07 - 0 and CO-SYS -> F11- 1
0
All* CO1-> F02 - 1: Optimization active;
Options:
* Function block parameter:
Advance heating time / 0 to 360 (120) min
0
All* CO1 -> F03 - 1 only with CO1 -> F01 - 1
Function block parameter:
Cycle time / 1 to 100 min (10 min)
Function block cannot be selected if
CO1 -> F07 - 0 and CO-SYS -> F11 - 1
0
All* CO1 -> F04 - 1: 4-point characteristic
CO1 -> F04 - 0: Gradient characteristic
0
All* CO1 -> F05 - 1 only with CO1 -> F07 - 1;
Options:
Function block parameter:
Delay / 1 to 6 °C/h (3 °C/h)
1
Types 5244 or 5257-5 Room Panels
2
Standard sensor
1
ON acc. to t
, set-back acc. to schedule*,
A
only with CO1 -> F07 - 1
2
ON acc. to t
, OFF acc. to room sensor*,
A
only with CO1 -> F01 - 1 and CO1 -> F07 - 1
3
ON and OFF according to room sensor,
only with CO1 -> F01 - 1
1
When outdoor temperature t
2
When outdoor temp. t
Appendix
decreases
A
decreases and increases
A
EB 5433 EN
77