ABB i-bus KNX SUG/U 1.1 Product Manual page 46

Split unit
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
28
This object indicates the status of horizontal swing.
1 = horizontal swing started
0 = horizontal swing stopped
29
Receipt of a telegram with the value 1 on this object activates the Boost function. The split unit switches to the highest fan
speed and swing is activated.
After the parametrized duration the split unit returns to its original state.
30
This object indicates the status of the Boost function.
1 = Boost function is activated
0 = Boost function is deactivated
44 2CDC508171D0201 | SUG/U 1.1
Function
Status Horizontal swing
Dependent on parameters
Boost
Dependent on parameter
Status Boost
Dependent on parameters
Group object name
Split unit
Enable "Swing" and
Enable group object "Status Swing" 1 bit
See Enable "Swing"
(horizontal and vertical), p. 24
Function
Enable "Boost" function
Function
Enable "Boost" function and
Enable group object "Status Boost" 1 bit
Data type
Flags
1 bit
C, R, T
DPT 1.003
1 bit
C, W
DPT 1.001
1 bit
C, R, T
DPT 1.001

Advertisement